Low Cracking Pressure
Very low cracking pressures of approximately 4–6 mbar allow the valves to be used even at very low operating pressures.
Safe gas flow direction in industrial gas supply systems: IBEDA GRV and GRS protect pipelines, tapping points and thermal process systems against hazardous gas return.
Gas return occurs when pressure differences or an incorrect operating condition cause gas to flow back against the intended direction of flow. In gas supply systems, this can result in an undesirable operating condition or the formation of a hazardous gas mixture.
IBEDA devices according to DIN EN ISO 5175-2 use a non-return valve and are designed without an integrated flame arrestor. The product range distinguishes between gas non-return valves (GRV) and flashback-resistant gas non-return safety devices (GRS) for defined fuel gas/compressed air applications.
The two series differ primarily in their intended safety function with regard to flashback.
| Feature |
GRV Gas Non-Return Valve |
GRS Gas Non-Return Safety Device |
|---|---|---|
| Standard | DIN EN ISO 5175-2 | DIN EN ISO 5175-2 |
| Prevents gas return | Yes | Yes |
| Integrated flame arrestor | No | No |
| Flashback – fuel gas / compressed air | No | Yes, except acetylene |
| Fuel gas / oxygen | Not for flashback protection | Not for flashback protection |
| Typical purpose | Prevention of gas return | Prevention of gas return + defined flashback protection |
The IBEDA valve system is designed for industrial gas supply systems and thermal process systems.
Very low cracking pressures of approximately 4–6 mbar allow the valves to be used even at very low operating pressures.
The valve design allows position-independent installation and facilitates integration into different system configurations.
Several nominal sizes up to DN 50 cover different flow requirements in pipeline systems and gas supply systems.
Depending on the application and gas medium, the valves are available in brass or stainless steel.
A large filter surface protects the valve system against contamination and ensures a long service life.
Functional and leak tightness testing ensures that only fully tested valves leave the factory.
Gas non-return valves and gas non-return safety devices are used wherever gas return into pipelines or gas supply systems must be reliably prevented.
Protection of thermal process plants based on or in accordance with EN 746-2.
Protection against gas return in central and decentralized pipeline systems.
Protection at the transition from the gas supply system to the consumer.
Integration into industrial gas distribution and gas supply systems.
The key criteria for product selection are gas type, process, maximum operating pressure, required flow rate, material and connection.
Key answers for selecting between GRV, GRS and flashback arrestors according to ISO 5175-1.
A flashback-resistant gas non-return valve prevents gas from flowing back against the intended direction of flow in pipeline systems or gas supply systems. IBEDA distinguishes between GRV gas non-return valves and GRS gas non-return valves (flashback resistant).
GRV gas non-return valves prevent gas return. GRS gas non-return valves also prevent gas return and are additionally designed to withstand flashbacks involving suitable fuel gas/compressed air mixtures. Neither product type according to ISO 5175-2 has an integrated flame arrestor.
No. For protection against flashback in fuel gas/oxygen systems, flashback arrestors according to DIN EN ISO 5175-1 with an integrated flame arrestor are required..
Typical applications include thermal process plants according to EN 746-2, pipeline systems, gas supply systems and tapping points.
The IBEDA valve system is designed for low cracking pressures of approximately 4 to 6 mbar. This allows the valves to be used in applications with very low operating pressures. The valve design also allows position-independent installation.
The IBEDA valve system is designed for low cracking pressures of approximately 4 to 6 mbar. This allows the valves to be used in applications with very low operating pressures. The valve design also allows position-independent installation.
IBEDA has matched the installation lengths of the corresponding valves to the former Gerätebau Insul models 1.123, 1.123F, 448, 448F, 449 and 449F. This allows replacement in many existing installations without modification of the installation dimensions.
Gas type, operating pressure, flow rate, nominal size and material help determine the appropriate GRV or GRS version.
Go to Product Finder Technical Advice